My PFX-series fan didn’t shut down with a Fire Alarm Test

 

Are you needing your Powerfoil X, X2.0, X3.0 or X4 model fan to comply with NFPA regulations? X-series fans require a contact closure on alarm condition between VFD terminals “DCM” and “MI3” to shut down with an “external fault” status. A PAM-SD model relay is factory-installed in the Normally Open configuration on these terminals and requires 20-32vdc at 15mA to change state. Follow these troubleshooting steps.

 

1. Lockout and tag out the fan appropriately.

2. An electrical multi-meter capable of testing DC voltage and continuity should be used to verify the relay functionality.

3. The PAM relay could be temporarily replaced with a “jumper” wire to test the programmable fault response function of the MI3 input when re-energized.

4. The factory-included relay may be replaced with another type if required, such as a proprietary addressable relay, but it must be installed in the N.O. configuration.

5. Record the model and serial number information found on or inside the VFD enclosure (varies by model/series) and contact Customer Support.

 

Still need help?

Contact one of our airflow experts today. Our customer Service hours: M-F 8 am – 6 pm EST

Phone Icon

Phone Support

Need Help?

Have A Question?