Powerfoil 6 HVLS Fan Support

Home » Support » Industrial Ceiling Fans » Powerfoil 6 HVLS Fan

About Powerfoil 6 HVLS Fan

Do I need to install guy wires with my Powerfoil 6 fan?
Yes, guy wires are required if:

  • The extension tube is 4 ft (1.2 m) or longer
  • The fan is installed outdoors
  • The fan is near fixtures or exposed to high wind
  • They are included in qualifying fan packages and are critical for stability and warranty compliance.
What kind of electrical circuit do I need for installation?
Each fan requires a dedicated overcurrent-protected circuit:

  • 20 A @ 200–240 VAC, single-phase
  • 15 A @ 200–240 VAC, three-phase
  • 10 A @ 400–480 VAC, three-phase
    Refer to NEC Article 430 and local codes for conductor sizing and protection requirements.
Can I mount Powerfoil 6 to any beam or structure?
Powerfoil 6 can be mounted to:

  • I-beams (with restrictions)
  • Bar joists (with angle iron)
  • Solid beams and Z-purlins (with special kits)

However, fabricated I-beams and strut channels (Unistrut) are not recommended unless approved by a structural engineer.

How do I maintain my Powerfoil 6 fan?
Big Ass Fans recommends:

  • An annual inspection of hardware, guy wires, and safety cables
  • Checking for oil leaks, cracks, or corrosion
  • Ensuring proper torque on bolts and fasteners
  • Cleaning with non-chlorine-based degreasers
    See the full Annual Maintenance Checklist in the installation guide.
What should I do if my fan doesn’t start after installation?
  • Check all power and control wiring for secure connections
  • Ensure the circuit is providing the correct voltage and amperage
  • Make sure any fire relay wiring is properly configured
    If issues persist, contact Big Ass Fans Customer Service at 877.244.3267.

Still Need Help?

Call our exceptional customer service team for help with all your fan-related questions.